Firetight firestop for a passive fire protection
Firetight Fire Stop

FIRE STOP: Passive fire protection in the unventilated facade

Firetight is a specially developed solution for airtight sealing of cavity walls in buildings, which also immediately makes the cavity fire-retardant. Firetight can make rooms in buildings fire-retardant sealed, so that a potential fire cannot simply spread to adjacent areas.

Firetight can be used anywhere in a building, where the cavity between floors, walls and facades must be able to withstand a fierce and expanding fire for a longer period of time.
Firetight prevents fire spreading between different floors in high buildings, such as residential towers, hospitals, offices, etc.

Advantages of FIRETIGHT Fire Stop

  • Has an extremely high fire resistance (up to 3+ hours EI)
  • Can be accurately dimensioned in advance and can be inspected afterwards
  • Can be installed quickly and easily without the need for additional fasteners
  • Contributes to the facade insulation (lambda 0.034 W / m.K)
  • Follows movements of expansion, contraction or wind load of the facade
  • Greatly improves the airborn sound insulation of the construction
  • Weather resistant and can be placed during the structural work
  • Sustainable and recyclable

For a ventilated facade we recommend our open-state cavity barrier FIRETIGHT FUSE.
010 302 0200Call us now

Firetight Fire Stop

Application

The Fire Stop consists of a vacuum-sealed strip of high-density Rockwool Premium wrapped in a PE foil vapor-barrier, with an added intumescent fire-retardent strip. fter placing and puncturing the vacuum foil, the wool expands and the Fire Stop completely fills the entire space. The product self-fixates itself in the cavity without the use of fasteners or glue. Designed for easy installation and disassembly.

With wide cavities, instead of a single row of Firetight, one can use double row Firetight to fill the space. The realized connection is thermally insulated, airtight and fire resistant for three to four hours.

The FIRETIGHT Fire Stop is available for the following cavity widths:
 

Dimensions

Cavity width

Cavity width

Cavity width

Cavity width

1200 x 250 mm

30 - 40 mm

40 - 55 mm

55 - 65 mm

70 - 80 mm

1200 x 300 mm

30 - 40 mm

40 - 55 mm

55 - 65 mm

70 - 80 mm

1200 x 400 mm

30 - 40 mm

40 - 55 mm

55 - 65 mm

70 - 80 mm

 
For wider cavities (up to 160mm), instead of a single rowm, a double row of Fire Stop can be used to fill the space.

 



 

Fire resistance -  FIRETIGHT Fire Stop

Application width 

Prestatie

Norm

40  – 90 mm
(Single)

EI240-H-M7.5-F-W40-90

EN 1366-4:2006+A1:2010)

40  – 100 mm
(double)

EI180-H-M7.5-F-W40-100

EN 1366-4:2006+A1:2010)

40  – 160 mm
(double)

EI120-H-M7.5-F-W40-160

EN 1366-4:2006+A1:2010)

 
The complete fire report of FIRETIGHT Fire Stop by Efectis is available upon request.
Related products
Firetape
View product
FIRETIGHT Fuse
View product
Airtape
View product
Airtight Airstop
View product